                                                                    182 - 03/18
   DUCTMATE RECTANGULAR DUCT CONSTRUCTION STANDARDS
                                                   TABLE OF CONTENTS
                 2     Forward / Tables
                 4     Table 2-29: Intermediate Reinforcement
                 5      EZ ROD / TIE ROD CONSTRUCTION USE FOR SHOP FABRICATED OR KNOCKED 
                       DOWN DUCTWORK
                 6     Senario A - Example Duct Construction Internal/External Reinforcements
                 7     Senario B - Example Duct Construction Internal/External Reinforcements
                 8     Table 1: 0.5” W.G. STATIC POS./NEG.
                 9     Table 2: 1” W.G. STATIC POS./NEG.
                 10    Table 3: 2” W.G. STATIC POS./NEG.
                 11    Table 4: 3” W.G. STATIC POS./NEG.
                 12    Table 5: 4” W.G. STATIC POSITIVE
                 13    Table 6: 6” W.G. STATIC POSITIVE
                 14    Table 7: 10” W.G. STATIC POSITIVE
                 15    Table 8 - DM45: 0.5” - 10” W.G. STATIC POSITIVE / 0.5” - 3” W.G. STATIC NEGATIVE
                 16    ALUMINUM CONSTRUCTION GUIDELINES
                 17    Table 9: 1” W.G. POSITIVE - ALUMINUM
                 18    Table 10: 2” W.G. POSITIVE - ALUMINUM
                 19    Table 11: 3” W.G. POSITIVE - ALUMINUM
                 20    Table 12: 4” W.G. POSITIVE - ALUMINUM
                 21    Table 13: 6” W.G. POSITIVE - ALUMINUM
                 22    Table 14: 10” W.G. POSITIVE - ALUMINUM
                 METRIC:
                 23    METRIC Forward / Tables
                 25    Table 2-29M: Intermediate Reinforcement
                 26     EZ ROD / TIE ROD CONSTRUCTION USE FOR SHOP FABRICATED OR KNOCKED 
                       DOWN DUCTWORK
                 27    Senario A - Example Duct Construction Internal/External Reinforcements
                 28    Senario B - Example Duct Construction Internal/External Reinforcements
                 29    Table 15: 125 PA STATIC POS./NEG.
                 30    Table 16: 250 PA STATIC POS./NEG.
                 31    Table 17: 500 PA STATIC POS./NEG.
                 32    Table 18: 750 PA STATIC POS./NEG.
                 33    Table 19: 1000 PA STATIC POSITIVE
                 34    Table 20: 1500 PA STATIC POSITIVE
                 35    Table 21: 2500 PA STATIC POSITIVE
                 36    Table 22 - DM45: 125 - 1500 PA STATIC POSITIVE / 125 - 750 PA STATIC NEGATIVE
                 37    ALUMINUM CONSTRUCTION GUIDELINES
                 38    Table 23: 250 PA POSITIVE - ALUMINUM
                 39    Table 24: 500 PA POSITIVE - ALUMINUM
                 40    Table 25: 750 PA POSITIVE - ALUMINUM
                 41    Table 26: 1000 PA POSITIVE - ALUMINUM
                 42    Table 27: 1500 PA POSITIVE - ALUMINUM
                 43    Table 28: 2500 PA POSITIVE - ALUMINUM
                 44 NOTES
                                                                                                                                1
   DUCTMATE RECTANGULAR DUCT CONSTRUCTION STANDARDS
                                                       FORWARD
               The widespread use of the “Ductmate® 25, 35, and 45 Slide-On Systems” makes these duct 
               construction guidelines a necessity.
               This manual is based on fundamental, sound engineering principles.  The criteria used to 
               establish the tables in this publication are 1⁄ ” joint and 3⁄ ” sheet deflection limits for ducts over 
                                                          4            4
               24” wide.
               These duct construction standards are based on independent testing using the Ductmate 
               Systems exclusively as manufactured by Ductmate Industries Incorporated U.S.A. No other 
               flange system can be used in conjunction with these tables. 
               Any reference to SMACNA in this manual refers to the SMACNA 2005 “HVAC Duct Construction 
               Standards, Metal and Flexible,” Third Edition.
                                                         TABLES
               When using the Rectangular Duct Construction Tables in this manual, Reinforcement Spacing 
               refers to both the Ductmate joints and Intermediate Reinforcements (Center Tie Rods or 
               External Stiffeners.)
               Ductmate’s Rectangular Duct Construction Tables are based on 6’, 5’, and 4’ duct section 
               lengths.  Columns 6’, 5’, and 4’ are construction guidelines without the use of any joint or 
               intermediate reinforcements.
                        1
               The 3’, 2 ⁄2’, and 2’ columns are used in conjunction with the 6’, 5’, and 4’ duct section lengths.  
               These columns provide alternative construction guidelines such as lighter metal gauges, joint tie 
               rods, center tie rods, or external intermediate reinforcements.
               When making special fittings, if the duct length matches the 3’, 21⁄ ’, and 2’ column spacing, you 
                                                                                 2
               do not need the CTR or external reinforcement between the joints. 
               See examples on pages 6-7.
               Positive/Negative Pressure
               This addendum includes positive pressure guidelines for pressure classes up to 10” w.g.
               Duct construction tables for 1⁄ ”, 1”, 2”, and 3” w.g. can be used for both positive and negative 
                                            2
               pressures.  For negative pressures greater then 3” w.g., please contact Ductmate Industries or 
               refer to the SMACNA Rectangular Industrial Duct Construction Standards.  Except for aluminum, 
               the guidelines on pages 8-15 can be used on galvanized, galvannealed, 304 and 316 stainless 
               steel, PVC coated, aluminized, and black iron.
               Duct construction guidelines for aluminum applications are on pages 17-22.
               Metric duct construction guidelines for aluminum can be found on pages 38-43.
               In a cell, DM25 refers to the Ductmate 25 Connector system, DM35 refers to the Ductmate 35 
               system, and DM45 refers to the Ductmate 45 system.
        2
The words contained in this file might help you see if this file matches what you are looking for:

...Ductmate rectangular duct construction standards table of contents forward tables intermediate reinforcement ez rod tie use for shop fabricated or knocked down ductwork senario a example internal external reinforcements b w g static pos neg positive dm negative aluminum guidelines metric m pa notes the widespread and slide on systems makes these necessity this manual is based fundamental sound engineering principles criteria used to establish in publication are joint sheet deflection limits ducts over wide independent testing using exclusively as manufactured by industries incorporated u s no other flange system can be conjunction with any reference smacna refers hvac metal flexible third edition when spacing both joints center rods stiffeners section lengths columns without provide alternative such lighter gauges making special fittings if length matches column you do not need ctr between see examples pages pressure addendum includes classes up pressures greater then please contact re...