146x Filetype PPTX File size 0.74 MB Source: www.entsoe.eu
Requirements for Wind Farms (WFs) Grid connection Frequency and Voltage Operation Boundaries • All WTGs should stay connected within the boundary 47.0 - 51.5 Hz • All WTGs should disconnect with no delay for system frequency < 47Hz • The disconnection of WTGs for system frequency > 51.5Hz takes place in 4 steps, with a 0.5sec delay between each step • In each step, 25% of the operating WTGs is disconnected • Applicable to all WFs 2 Requirements for Wind Farms (WFs) Grid connection Active/Reactive Power Boundaries Upper diagram : Q-V curve • Within the no-striped area (PF> 0.95) the WF should operate at it’s nominal capacity • Within the striped area (0.83510 MW Requirements for Wind Farms (WFs) Grid connection Voltage/Reactive Power Control • Upon TSO’s request, the WF should operate in voltage, reactive power or PF control mode – Voltage regulation is applied at system connection point (HV/150kV), reactive power and power factor regulation is applied at the MV (20kV) side of WF step up transformer • The WF should be equipped with voltage/reactive power regulator according a HV Q–V characteristic – The slope and the reference value Vset (zero reactive power injection at the MV (20kV) side of WF step up transformer are defined by the TSO • The desired value of the controlled quantity should be implemented within 30sec after signal receiving • speed of regulation response : – in a voltage step change at the connection point (or a step change of reactive power or power factor reference value) the reactive power of the WF should reach 90% of the steady state value in less than 1s • Applicable to WFs with installed capacity > 10 MW Requirements for Wind Farms (WFs) Grid connection Load-Frequency control • At TSO’s command, the WF should change the active power ramp up/down rate (±MW/min) – Min and max limits of ramp up/down rates are set by the TSO – Active power measurement applies at the MV (20kV) side of WF step up (150/20) transformer • The WF should be equipped with a load- frequency controller (characteristic f-P) – Frequency measurement precision ±10mHz – Points Β and Γ define a dead zone within the WF should operate with a constant percentage (% P/Pmax) of the available active power – Table values are defined by the TSO • TSO’s command for reduction of the production should be implemented within 60s after signal receiving • Applicable to WFs with installed capacity > 10 MW Requirements for Wind Farms (WFs) Grid connection Low Voltage Ride Through capability • Applicable to all WTGs, voltage is measured at the HV connection point • Disconnection is allowed in area 1 – Reconnection after fault clearance, within 2sec, with a rate 10-20% Pmax/sec • Disconnection is allowed in area 2 – Disconnection in 4 steps, with 0.3sec delay between each step, shed 25% of WFs WTGS at each step – Reconnection when the voltage at the connection point (HV) is greater than 142,5kV or 380 kV • After fault clearance, WTGs not disconnected should increase their production with a rate of 10- 20% Pmax/sec • Reactive current control – WTG nominal values Ηare the reference values – For a ±10% Vnom voltage change, the control is activated within 20msec after fault detection – Provision of reactive current ± 2% Ιnom for each ±1% ΔVnom – For voltage sags 50% Vnom , provision of reactive current +100 % Ιnom within 70 msec after fault detection – Provision of reactive current applies for 500 msec after voltage recovery within ±10% Vnom band
no reviews yet
Please Login to review.